S135 – Emergency disconnect switch up to 320 V DCS005 – Cam switch elements
S135 – Emergency disconnect switch up to 320 V DCContactorsRequest
1454bookmark
S005 – Cam switch elementsContactorsRequest
2702bookmark
Series S135 S005
Type of voltage DC
Main contacts, configuration 1 x or 2 x NC 1 NC
Nominal voltage Un 300 V
Rated insulation voltage Ui 320 V 400 V
Rated impulse withstand voltage Uimp 4 kV
Conv. thermal current Ith 160 A 15 A
Breaking capacity 220 V DC, 630 A, 6 ms with arc chamber (inductive load)
Permissible inrush current 720 A at resistive load
Mechanical endurance > 30,000 operating cycles > 1 million operations
IP rating (IEC 60529) IP00 IP00
Mounting orientation any
Terminals screw-type M8 or M10 M5
Permissible tightening torque M8: 6 Nm max., M10: 10 Nm max.
Temperature range -25 °C ... +50 °C -25 °C ... +70 °C
Weight 650 approx. 35 g