S132 – Emergency disconnect switch up to 160 V DCS134 – Emergency disconnect switch up to 160 V  DC
S132 – Emergency disconnect switch up to 160 V DCContactorsRequest
1449bookmark
S134 – Emergency disconnect switch up to 160 V  DCContactorsRequest
1453bookmark
Series S132 S143
Mechanical endurance 30,000 operating cycles > 30,000 operating cycles
IP rating (IEC 60529) IP00 IP00
Mounting orientation any any
Terminals screw-type M8 screw-type M8, M10
Type of voltage DC DC
Main contacts, configuration 1 x NC 1 x NC
Nominal voltage Un 100 V 100 V
Rated insulation voltage Ui 160 V 160 V
Rated impulse withstand voltage Uimp 4 kV at PD3 4 kV bei PD3
Conv. thermal current Ith 125 A 250 A
Permissible inrush current 600 A 1,500 A
Rated operating current Ie at 24 V: 250 A, at 48 V: 200 A, at 80 V: 150 A 24 V DC, L/R=15 ms: 300 A, 80 V DC, L/R=15 ms: 250 A
Max. breaking capacity 24 V DC, L/R=15 ms: 1,000 A, 48 V DC: 800 A, 80 V DC: 600 A 24 V DC, L/R=15 ms: 1,200 A, 80 V DC, L/R=15 ms: 1,000 A